- AGP-3300H
- AGP3300H-L1-D24-RED
- 5.7" (Handheld)
Documentation
Support
Quick Information
Software
Certifications
Functional Specifications
Display Type | Monochrome LCD
|
---|---|
Display Size | 5.7"
|
Resolution | 320 x 240 pixels (QVGA)
|
Dot pitch | W0.36 x H0.36 mm [W0.01 x H0.01 in.]
|
Effective Display Area | W117.2 x H88.4 mm [W4.61 x H3.48 in.]
|
Display Colors | Monochrome (16 Levels)
|
Backlight | White LED (User nonreplaceable parts, return system to distributor.)
|
Brightness Control | 16 Levels (Adjusted with the touch panel)
|
Contrast Control | 8 Levels (Adjusted with the touch panel)
|
Language Fonts | Japanese: 6,962 (JIS Standards 1 & 2) (including 607 non-kanji characters), ANK: 158 (Korean fonts, Simplified Chinese and Traditional Chinese fonts are downloadable.
|
Character Sizes | Standard font: 8 X 8, 8 X 16, 16 X 16 and 32 X 32 pixel fonts, Stroke font: 6 to 127 pixel fonts
|
Font Sizes | Standard font: Width can be expanded up to 8 times., Height can be expanded up to 8 times.
|
8 x 16 dots | 40 char. x 15 rows
|
16 x 16 dots | 20 char. x 15 rows
|
32 x 32 dots | 10 char. x 7 rows
|
8 x 8 dots | 40 char. x 30 rows
|
Application Memory | FLASH EPROM 6 MB*1
|
Data Backup | SRAM 320KB (uses lithium battery)*2
|
Clock Accuracy | 65 sec/month (deviation at room temperature and power is OFF)*3
|
Touch Panel Type | Resistive Film (analog)
|
Touch Panel Resolution | 1,024 X 1,024
|
Touch Panel Service Life | 1,000,000 times or more
|
No. of Key Switches | None
|
Serial (COM1) | RS-232C/422/485, Asynchronous Transmission, Data Length: 7 or 8 bit, Parity: none, Even or Odd, Stop Bit: 1 or 2 bit, Data Transmission Speed: 2,400 bps to 115.2 kbps, 187.5 kbps(MPI), Connector: D-Sub9 (plug)
|
Ethernet (LAN) | IEEE802.3i/IEEE802.3u, 10BASE-T/100BASE-TX, Connector: Modular jack (RJ-45) x 1
|
USB (TYPE-A) | Conforms to USB1.1. (TYPE-A conn.) X 1, Power Supply Voltage: DC5V±5%, Output Current: 500mA (max.), Communication Distance: 5m (max.)
|
CF Card | Compact Flash CF Card Slot (TYPE-II) X 1
|
Function Switch | 12 switches (Right: 6 switches, Left: 6 switches) (DOUT: 2 Open Collector Output [F1, F2], Operation Switch: 1 Open Collector Output [O.P])
|
Emergency Switch Output | Push-lock switch, 3 contacts (a-contact: 1 contact, b-contact: 2 contacts), Rated voltage: DC 30 V, Maximum rated current: 1 A, (Minimum allowable load: DC 5 V, 1 mA), Applicable standards: IEC/EN60947-5-1, IEC/EN60947-5-5, UL508, CSA C22.2 No.14
|
3-Position Enable Switch Output | GP Rear panel switch, 2 contacts (a-contact), Rated voltage: DC 30 V, Maximum rated current: 700 mA (Minimum allowable load: DC 3 V, 5 mA), Applicable standards: ICE/EN60947-5-8, UL508 (UL approval), CSA C22.2 No.14 (UL approval), ISO12100/EN292, IEC/EN60204-1, ISO11161/prEN11161, ISO10218/EN775, ANSI/RIA R15.06, ANSI B11.19
|
Operation Output | Open Collector Output: 1 point, Rated Voltage: DC 24 V, Maximum Rated Current: 300 mA*4
|
External Buzzer Output | Open Collector Output 1 point, Rated Voltage: DC 24 V, Maximum Rated Current: 300 mA*5
|
DOUT Output | Open Collector Output: 2 points [F1, F2], Rated Voltage: DC 24 V, Maximum Rated Current: 300 mA/point*6
|
1Capacity available for user application.
2A Lithium battery's lifetime is:
10 years when the battery's ambient temperature is 40 oC or less.
4.1 years when the battery's ambient temperature is 50 oC or less.
1.5 years when the battery's ambient temperature is 60 oC or less.
When used for back up: Approximately 100 days, with a fully charged battery.
Approximately 6 days, with a half-charged battery.
3Depending on the operating temperature and age of unit, the clock can deviate from -380 to +90 sec./month. For systems where this level of deviation is a problem, the user should monitor and make adjustments when required.
4To use GP's external output interface eg. DOUT and build a system, Pro-face's dedicated Cable with Connector and Conversion Adapter (AGP3000H-ADPCOM-01) are required.
5To use GP's external output interface eg. DOUT and build a system, Pro-face's dedicated Cable with Connector and Conversion Adapter (AGP3000H-ADPCOM-01) are required.
6To use GP's external output interface eg. DOUT and build a system, Pro-face's dedicated Cable with Connector and Conversion Adapter (AGP3000H-ADPCOM-01) are required.
General Specifications
International Safety Standards | |
---|---|
Rated Input Voltage | DC 24V
|
Input Voltage Limits | DC 19.2 to 28.8V
|
Allowable Voltage Drop | 10 ms or less
|
Power Consumption | 16.7W (max.)
|
In-Rush Current | 60 A or less, Half width (Time duration with a current exceeding 30 A): 40 µs or less
|
Voltage Endurance | AC 500V 20mA for 1 minute, (between charging and FG terminals)
|
Insulation Resistance | DC500V 10MΩ (min.), (between charging and FG terminals)
|
Surrounding Air Temperature | 0 to 40°C
|
Storage Temperature | -20 to 60 °C (-4 to 140 °F)
|
Ambient Humidity | 10 to 90% RH (Wet bulb temperature: 39°C max. - no condensation.)
|
Storage Humidity | 10 to 90% RH (Wet bulb temperature: 39°C max. - no condensation.)
|
Dust | 0.1 mg/m³ or less (non-conductive levels)
|
Pollution Degree | For use in Pollution Degree 2 environment
|
Atmosphere | Free of corrosive gases
|
Air Pressure (altitude range) | 800 to 1,114 hPa (2,000 m [6,561ft.] above sea level or less)
|
Vibration Resistance | IEC/EN61131-2 compliant, 5 to 9Hz Single amplitude 3.5mm [0.14in.], 9 to 150Hz Fixed acceleration: 9.8m/s², X,Y,Z directions for 10 cycles (100 minutes)
|
Concussion Resistance | IEC/EN61131-2 compliant, 147m/s² X,Y,Z directions for 3 times
|
Noise Immunity | Noise Voltage: 1,000Vp-p, Pulse Duration: 1µs, Rise Time: 1ns, (via noise simulator)
|
Noise Immunity (Fast Transient Burst Noise) | Power Line: 2kV (IEC/EN61000-4-4), COM Port: 1kV (IEC/EN61000-4-4)
|
Electrostatic Discharge Immunity | Contact Discharge Method: 6kV (IEC/EN61000-4-2 Level 3)
|
Electromagnetic Compatibility (EMC) | Normal Mode: 1kV Common Mode 2kV (IEC/EN51000-4-2 Level 3)
|
Drop Resistance | IEC/EN61131-2 compliant, 1.0 meter drop - 2 times
|
Grounding | Functional grounding:Grounding resistance of 100Ω, 2mm² orthicker wire, or your country's applicable standard.(Same for FG and SG terminals)
|
Structure | Equivalent to IP65f (on the front panel when properly installed in an enclosure)*7
|
Weight Approx. | 1 kg [2.2 lb] or less (display unit only)
|
7The front face of the GP unit, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the specification. Even though the GP unit's level of resistance is equivalent to these standards, oils that should have no effect on the GP can possibly harm the unit. This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to adhere to the unit for long periods of time. If the GP's front face protection sheet becomes peeled off, these conditions can lead to the ingress of oil into the GP and separate protection measures are suggested., Also, if non-approved oils are present, it may cause deformation or corrosion of the front panel's plastic cover. Therefore, prior to installing the GP be sure to confirm the type of conditions that will be present in the GP's operating environment., If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from the panel, the original level of the protection cannot be guaranteed. To maintain the original protection level, be sure to replace the installation gasket regularly.